Masonry Design Question

4/30/2021

10 Comments

 
The contractor on our job is pointing out small cracks and holes that need to be repaired/filled etc. I have been in the masonry industry for half a century and respect good workmanship but I think the imperfections that the contractor is pointing out are not significant or reasonable.
The wall is to receive direct applied stucco thus we are cutting the joints flush.
My question is - what are the criteria for judging whether or not an imperfection in a masonry wall should be acceptable.
The simple answer is that unless the specifications specifically call out for a special criteria for workmanship the codes contain one universally accepted criteria – view at 20 ft under diffused lightning. Period. This is in section 7.2 of ASTM C90-14. The current version of C90 referenced in the 7th Edition Florida Building Code is 2014.

It is understood that full head joints and bed joints are called out in the TMS 602 Code (current referenced edition is 2016) but there is no further guidance given. A mock up panel, if built and agreed on prior to construction, would govern for workmanship. In the absence of a mock up panel you are left with that most rare of commodities – common sense.

So, on the basis of common sense lets think about where our only code based criteria, 20’ in diffused lighting, might or might not apply.

It probably wouldn’t apply for the installation of a glazed block in an 8’x10’ bathroom. In that case your mortar joints are going to be expected to approach perfection. Any imperfections are going to be visible. Since the joint is tooled the mason at least has a fighting chance of striking the joints with a high degree of care.

Our 20’ criteria is regularly used for architectural block in an exterior wall. Cracks and holes that are not visible at 20’ under diffused lighting are considered acceptable.

In the case of block substrate to receive a direct applied stucco coating the 20’ criterial would be considered adequate for several reasons. The first is that the joints are not tooled. The joints must be cut flush so that they do not reflect through the finished stucco. Without tooling complete densification of a mortar joint is not possible. The second reason is that the direct applied stucco is the exterior weather barrier. There should absolutely be a solid block and filled mortar joint behind the stucco but the stucco itself is your primary protection. The third reason is that there are no esthetics issues.
​
My view is that without a mock up panel and without job specifications specific to the appearance of the mortar joints, the 20’ diffused lighting rule would govern as the only applicable code guidance.
10 Comments

    Authors:

    Picture
    Jerry Painter, FASTM
    352-378-7511
    [email protected] 

    Picture
    Don Beers, PE, GC
    561-310-9902
    [email protected]

    Categories

    All
    #5 Rebar
    Backer Rod
    Backup Wall
    Bar Hooks
    Block Strength
    Bond Beam
    Bond Breakers
    Brick
    Brick Veneer
    C129
    C90
    Cavity Wall
    Cell Size
    Cell Width
    Cmu
    Code Editions
    Code Requirements
    Codes
    Concrete Block
    Concrete Interlocking Pavers
    Concrete Pavers
    Construction Guidance
    Control Joint
    Control Joints
    Corner Attachments
    Cracking
    Crosswebs
    De-bonded Veneer
    Density
    Design Criteria
    Driveway
    Energy
    Energy Efficiency
    Energy Loss
    Envelope Leakage
    Expansion Joints
    FBC
    FBC 6th Edition
    FBC 7th Edition
    Filling Cells
    Fine Aggregate Grout
    Fire Rating
    Florida Building Code
    F''m
    Grouted Beam
    Grout Height
    Grouting
    Grouting Of Block Walls
    High Strength Masonry
    High-strength Masonry
    High Wind
    High Wind Construction
    HJR
    Horizontal Steel Spacing
    ICC 600
    ICC Code
    Infill
    In-plane
    Insulation
    Integral Waterproofing
    Interlocking Pavers
    Intermediate
    Intersecting Walls
    Job Requirements
    Jobsite
    Joint Reinforcement
    Light-weight
    Masonry
    Masonry Construction
    Masonry Details
    Masonry Insulation
    Masonry Websites
    Masonry Workmanship
    Max Bar Size
    Missile Impact
    Mortar
    Mortar Joints
    Net Area Strength
    Out-of-plane
    Perm
    Pnnl
    Psi
    Rebar
    Reinforcement
    Residential
    R Value
    Safety
    Setting Pavers
    Shear Walls
    Shrinkage
    Slip Joints
    Sound Insulation
    Sound Transmission
    Split-face Block
    STC Rating
    Sticky Stone
    Stucco
    Stucco Bonding
    Stucco Over Lath
    Table 2
    Thin Veneer
    Tie Beams
    TMS
    TMS 402/602
    Tyvek
    UL
    UL Labeling
    Vapor Barrier
    Vertical Steel
    Vertical Walls
    Videos
    Wall Bending
    Wall Design
    Wall Tolerances
    Water Intrusion
    Waterproofing
    Water Vapor
    Wind

    Archives

    May 2024
    April 2024
    March 2024
    March 2022
    February 2022
    January 2022
    October 2021
    August 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    October 2020
    September 2020
    August 2020
    July 2020
    May 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    April 2018
    March 2018

    RSS Feed

Masonry Resources

Clay Brick Masonry
Concrete Masonry
Mortar & Grout
Reinforcing Steel
Sustainability & LEED
Wall System Comparisons


MAF Websites

​Find out more about Masonry
​Pre-Apprentice Programs by visiting:
www.MasonryEducation.org
Picture
Masonry Association of Florida, Inc. |PO Box 24474 , Fort Lauderdale, FL 33307
Copyright  ©  2017. All Rights Reserved.
Sitemap
  • News
  • Knowledge Base
  • FloridaMasonry.com
  • CWFN Home